Particulars
|
Technical Particulars
|
|
Manufacturer's type/Designation/Installation
|
11 KV 200, A Tilting type
|
|
Manufacturer's name and country of manufacture
|
M/s. Jaipuria Brothers Electricals Pvt. Ltd., Delhi
|
|
Works Address
|
F-16 -17, Ganga Vihar, Gokul Puri Shahdara Delhi
|
|
Standard (s) according to which the isolators are manufactured
|
IS 9921/Part I to V
|
|
Maximum design voltage at which the isolators can operate
|
12 KV
|
|
Rated Frequency
|
50 Hz.
|
|
Rated Voltage
|
12 KV
|
|
Continuous current rating
|
200 A
|
|
Rated short time withstand current for one second
|
|
|
Voltage drop across terminals
|
As per relevant IS
|
|
Current density at the minimum cross section of :
|
|
|
For copper parts ( Amp. /sq . Mm)
|
Less than 2.5
|
|
For aluminum parts (Amp. Sq/ mm)
|
Less than 1.0
|
|
Maximum temperature rise of following current carrying parts when carrying rated current continuously (deg. C) over an ambient of 50 deg . C Instead of 40 deg. C mentioned in relevant IS
|
25oC
|
|
Class (outdoor)
|
Outdoor
|
|
Insulation levels.
|
|
|
impulse withstand voltage (KV peak)
|
|
|
Across the isolating distance
|
85 KV
|
|
Phase to earth
|
75 KV
|
|
Power Frequency withstand voltage (KV rms)
|
|
|
Phase to earth
|
28 KV
|
|
Across the isolating distance
|
32 KV
|
|
Minimum clearance in air (mm) center to center between phase to phase
|
600 mm
|
|
Minimum distance between insulators
|
As per drawing to be approved
|
|
Minimum Isolating distance (in open position)
|
375 mm
|
|
Design & Construction :
|
|
|
Number of insulators Per Pole
|
3 nos.
|
|
Number of breaks Per Pole
|
Single
|
|
Type of closing/opening mechanism
|
Vertical
|
|
Height of contacts
|
110 mm
|
|
Cross section and number of fixed contact leafs
|
2 nos., 38 mm x 3.0 mm thick
|
|
Cross section of moving blade
|
32 mm x 5 mm
|
|
Size and numbers of spring used in fixed contact
|
4 nos, 16 SWG, 28 mm long, 15 mm OD & 6 turns
|
|
All Current carrying copper parts should be suitable to have current density less than
|
2.5 A/ sq./mm
|
|
All Current carrying aluminum parts should be suitable to have current density less than
|
1.0 A/ sq/ mm
|
|
Operating pipe (handle & rod)
|
25 mm NB, 5.0 meter long med, class
|
|
Type of bearings
|
Rocking type lever supported on side plates with self lubricated nylon rings
|
|
Base channels
|
75 mm x 10 mm x 100 mm long
|
|
Post Insulators
|
|
|
Type
|
11 KV, E-22, IS 2544
|
|
Name of manufactures
|
Name of manufactures
|
|
Height of each insulator
|
245 mm
|
|
Tensile strength (Kg)
|
20 KN
|
|
Compressive strength
|
40 KN
|
|
Torsional strength in (Kg m)
|
340 MN
|
|
Cantilever strength upright
|
9 KN
|
|
Power frequency dry flash over voltage (KV) rms
|
As per relevant IS
|
|
Power frequency we flash over voltage (KV) rms
|
As per relevant IS
|
|
Impulse flash over voltage (positive wave ) (KV) peak
|
As per relevant IS
|
|
Impulse with stand voltage (KV) peak
|
75
|
|
Power frequency puncture voltage (KV) rms
|
As per relevant IS
|
|
Visible discharge voltage level (KV) rms
|
9
|
|
Cree page distance
|
300 mm (min)
|